Skip to Main Content »

Your shopping cart is empty
Call Us
Free Shipping

Fluke 975 AirMeter

Be the first to review this product

Availability: In stock

Excl. Tax: £1,558.00 Incl. Tax: £1,869.60
OR

Quick Overview

***CALL FOR BEST PRICE***

Please state which range when ordering.

The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time. The Fluke 975 measures:

Temperature
Velocity
Humidity
CO2
CO



Use the Fluke 975 AirMeter test tool to:

Respond to comfort-related calls from occupants.
Verify the operation of building HVAC control systems.
Determine whether adequate ventilation exists.
Monitor air flow and velocity.
Test for dangerous carbon monoxide leaks.
Perform duct traversals.
Optimize HVAC systems to manage energy costs

Fluke 975 AirMeter

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Details

The Fluke 975 offers an unparalleled featureset for HVAC and facilities technicians, helping them work more quickly and accurately, with the ease of use and durability customers expect from a Fluke meter.

Simultaneously measures, logs, and displays temperature, humidity, CO2, and CO on a bright, backlit LCD display
One-touch air flow and velocity with available probe*
Wet bulb and dew point temperature
% of outside air calculation
CO2 and CO field calibration feature
Self-test function at startup
Auto-backlight
Automatically compensates for barometric pressure changes
Min/Max/Average on all measured and calculated readings
Multi-language user interface
Metric or standard units
Audible and visual threshold alarms
Extensive discrete or continuous data logging capacity, downloadable to PC via USB interface
Keypad lock for security
Included FlukeView Forms® software

Measured specifications
Temperature Range: -20 °C to 50 °C (-5 °F to 122 °F)
Display resolution: 0.1 °C (0.1 °F)
Accuracy: ± 0.9 °C/± 1.62°F from 40 °C to 60 °C
± 0.5 °C/± 1.00°F from 5 °C to 40 °C
± 1.1 °C/± 1.98 °F from -20 °C to 5 °C

Relative humidity Range: 10 % to 90 % RH, non-condensing
Display Resolution: 1%
Accuracy: ± 2 % RH (10 % RH to 90 % RH)

Air velocity Range: 50.0 fpm to 3000 fpm
0.25 m/sec to 15 m/sec
Display Resolution: 1 fpm (0.005m/sec)
Accuracy: ±4 % or 4 fpm*
±4 % or 0.02 m/sec* whichever is greater
*Accuracy specification only valid for velocity readings above 50 fpm.

C0 Range: 0 to 500 ppm
Display Resolution: 1 ppm
Accuracy: ± 5 % or ± 3 ppm, whichever is greater, @ 20 °C and
50 % RH

C02 Range: 0 to 5000 ppm
Display Resolution:
1 ppm
Accuracy: Warm up time 1 min (5 minutes for full specification) 2.75% + 75 ppm



Calculated specifications
Dew point temperature Range: -44 °C to 50 °C, (-47 °F to 122 °F)
Display Resolution: 0.1 °C (0.1 °F)
Accuracy: ± 1 °C when temp: -20 °C to 50 °C RH: 40 % to 90 %
± 2 °C when temp: -20 °C to 50 °C RH: 20 % to 40 %
± 4 °C when RH: 10 % to 20 %

Wet bulb temperature Range: -16 °C to 50 °C, (3 °F to 122 °F)
Display Resolution: 0.1 °C, (0.1 °F)
Accuracy: ± 1.2 °C when RH: 20 % to 90 % temp: -20 °C to 60 °C
± 2.1 °C when RH: 10 % to 20 %

Volume flow rate (in a duct) Range: 0 to 3,965 M3/m, (0 to 140,000 cfm)
Display Resolution: 0.001 M3/min, (1 cfm)
Accuracy: N/A: The volume flow calculation will be a simple average of the data points times the duct area

% outside air (based on temperature) Range: 0 to 100%
Display Resolution: 0.1

% outside air (based on CO2) Range: 0 to 100 %
Display Resolution: 0.1 % N/A



General specifications
Operating and storage temperature: -20 °C to 50 °C (-4 °F to 122 °F)

Humidity 10 % to 90 % (non-condensing)

Altitude Up to 2000 m (6562 ft)

Shock and vibration MIL-PRF-28800F: Class 2

Multi-language interface English, French, Spanish, Portuguese and German

Battery Rechargeable Li-Ion (primary), three-AA (backup)

Data logging 25,000 records (continuous), 99 records (discrete)

Warranty Two-years


Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.